Product Overview
Applications
Measures voltage, current, energy, frequency, active power, reactive power and power factor.
Provides channel diagnostics, diagnostic alarms, limit value alarms and hardware interrupts for measured process values.
Technical Summary
| Product type | AI Energy Meter 480VAC ST |
|---|---|
| Usable BaseUnit | BU type D0 |
| Measurement functions | Voltage, current, energy, frequency, power, active power, reactive power and power factor |
| Supply | AC 100 – 277 V via voltage measurement channel L1 |
| Line frequency | 47 Hz to 63 Hz |
| Voltage measurement | Up to 480 V between line conductors |
| Current measurement | 1 % to 100 % relative to the secondary rated current 5 A; continuous AC current up to 5 A |
| Engineering | STEP 7 TIA Portal from V13 SP1; STEP 7 from V5.5 SP4 and higher |
| PROFINET and PROFIBUS | PROFINET from GSD V2.3; PROFIBUS from GSD Revision 5 |
| Product lifecycle | Product cancellation |
Key Features
Measures voltage, current, energy, frequency, power, active power, reactive power and power factor.
Measures line voltage up to 480 V between line conductors and continuous AC current up to 5 A; current measurement requires a current transformer.
Supply: AC 100 – 277 V via voltage measurement channel L1; permissible line frequency: 47 Hz to 63 Hz.
Has channel diagnostics, diagnostic and limit value alarms, hardware interrupts, and PWR, channel status, Fn and DIAG LEDs.
STEP 7 TIA Portal configurable/integrated from V13 SP1; PROFINET from GSD V2.3 and PROFIBUS from GSD Revision 5.
Mounting position: any. Dimensions: 20 mm width, 73 mm height and 58 mm depth.
Frequently Asked Questions
What is Siemens 6ES7134-6PA20-0BD0?
It is a SIMATIC ET 200SP AI Energy Meter 480VAC ST analog input module with channel diagnostics.
Which BaseUnit is usable with this module?
The usable BaseUnit is BU type D0. For the 2-wire connection variant, the source also lists BU20-P12+A0+0B.
What supply and line-frequency values does it use?
Supply is AC 100 – 277 V via voltage measurement channel L1, with a permissible line-frequency range of 47 Hz to 63 Hz.
How is this module mounted and what are its dimensions?
The mounting position is any. Dimensions are 20 mm width, 73 mm height and 58 mm depth.
Can this exact line item be included in a quotation?
Provide the requested quantity, destination, schedule context and any additional BOM lines for quotation review.