Product Overview
Applications
Measures frequency from 0.04 Hz to 800 kHz with quadruple evaluation.
Measures cycle duration from 1 μs to 25 s.
Measures velocity from 0 to 2 147 483 in configured units per selected time basis.
Technical Summary
| Product type | F-TM Count 1x1Vpp sin/cos HF |
|---|---|
| Channel capacity | 1 channel |
| Input signal | sin/cos 1 Vpp, centered at 2.5 V offset |
| Input frequency, max. | 200 kHz |
| Counting frequency, max. | 800 kHz; with quadruple evaluation |
| Supply voltage | 24 V DC |
| Encoder supply | 5.1 V ±3.5 %; output current up to 300 mA |
| BaseUnit | BU type A0 |
| Firmware version | V1.0 |
Key Features
1 channel for symmetrical incremental rotary encoders with sin/cos 1 Vpp signals.
Input frequency up to 200 kHz and counting frequency up to 800 kHz with quadruple evaluation.
5.1 V ±3.5 % supply with output current up to 300 mA and electronic overload protection.
Rated load voltage L+ is 24 V, with a permissible range from 20.4 V to 28.8 V and reverse polarity protection.
Supports Safe Operating Stop (SOS), Safely-Limited Speed (SLS), Safe Direction (SDI), and Safe Speed Monitor (SSM).
Suitable for BU type A0; shielded cable length up to 150 m. STEP 7 V17 or higher is configurable/integrated; use GSDML for prior versions.
Frequently Asked Questions
What is the exact configuration of Siemens 6ES7136-6CB00-0CA0?
It is a SIMATIC ET 200SP F-TM Count 1x1Vpp sin/cos HF module with 1 channel, PROFIsafe, and a pack quantity of 1 unit.
Which encoder signals does the module support?
It supports symmetrical incremental encoder signals with sin/cos 1 Vpp, including A/B tracks with 90° phase offset and A/B tracks with zero track.
What are the maximum input and counting frequencies?
The maximum input frequency is 200 kHz. The maximum counting frequency is 800 kHz with quadruple evaluation.
Which BaseUnit and cable length are supported?
The module is suitable for BU type A0 and supports shielded cable lengths up to 150 m.