Product Overview
Technical Summary
| Input | 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz |
|---|---|
| Rated output power (LO) | 30.00 kW | 40.00 hp |
| Rated output power (HO) | 22.00 kW | 30.00 hp |
| Rated current (LO) | 60.00 A |
| Rated current (HO) | 45.00 A |
| Output frequency for vector control | 0 … 200 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| Connections | M6 bolt; 10.00 … 35.00 mm2 (AWG 8 … AWG 2) |
| Degree of protection | IP20 / UL open type |
| Frame size | FSD |
| Configuration | Without control unit and BOP |
Key Features
Rated output power is 30.00 kW | 40.00 hp for LO and 22.00 kW | 30.00 hp for HO. The collected description specifies HO overload of 200% for 3 s, 150% for 57 s, and 100% for 240 s at 0 to +50 °C.
Input: 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz. Output: 3 AC, rated voltage 400V IEC | 480V NEC, with maximum output current of 90.00 A.
Output frequency is 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control. Pulse frequency is 4 kHz.
Line-side and motor-end connections use an M6 bolt with 10.00 … 35.00 mm2 (AWG 8 … AWG 2) conductor cross-section. Maximum motor cable length is 50 m (164.04 ft) shielded or 100 m (328.08 ft) unshielded.
Frame size: FSD. Dimensions are 512 mm high × 275 mm wide × 204 mm deep; net weight is 16.00 kg (35.27 lb). Degree of protection: IP20 / UL open type.
The power module has an integrated Class A filter and the collected configuration states regeneration capability. It is an Active Product and is without a control unit and BOP.
Frequently Asked Questions
What is the exact Siemens line item?
It is the Siemens 6SL3225-0BE32-2AA0 SINAMICS G120 PM250 power module.
What input and output ratings should be retained in the BOM?
Input is 3 AC, 380 … 480 V ±10 % at 47 … 63 Hz. Rated output power is 30.00 kW | 40.00 hp for LO and 22.00 kW | 30.00 hp for HO.
What connections and motor cable lengths are specified?
Both line-side and motor-end connections use an M6 bolt and 10.00 … 35.00 mm2 (AWG 8 … AWG 2) conductor cross-section. Maximum motor cable length is 50 m (164.04 ft) shielded or 100 m (328.08 ft) unshielded.
What is included in this configuration?
It is without a control unit and BOP; the collected configuration has an integrated Class A filter and regeneration capability.
What project details should accompany a quotation request?
Include the requested quantity, destination, schedule context, and any additional BOM line items for review.