Product Overview
Applications
The Power Module is capable of energy recovery.
Technical Summary
| Product type | SINAMICS G120 Power Module PM 250 |
|---|---|
| Input | 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz |
| Rated power (LO) | 11.00 kW | 15.00 hp |
| Rated power (HO) | 7.50 kW | 10.00 hp |
| Rated current (LO) | 25.00 A |
| Rated current (HO) | 19.00 A |
| Max. output current | 38.00 A |
| Control frequency | Vector control: 0 … 200 Hz; V/f control: 0 … 550 Hz |
| Integrated filter | Class A |
| Connections | Screw-type terminals; 2.50 … 10.00 mm2 (AWG 14 … AWG 8) |
| Degree of protection | IP20 / UL open type |
Key Features
Power low overload: 11 kW at 150% for 3 s, 110% for 57 s and 100% for 240 s at 0 to +40 °C ambient temperature. Power high overload: 7.5 kW at 200% for 3 s, 150% for 57 s and 100% for 240 s at 0 to +50 °C ambient temperature.
Input: 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz. Output: 3 AC, 11.00 kW (15.00 hp) LO or 7.50 kW (10.00 hp) HO.
Output frequency for vector control: 0 … 200 Hz. Output frequency for V/f control: 0 … 550 Hz. Pulse frequency: 4 kHz.
Line-side and motor-end connections use screw-type terminals for 2.50 … 10.00 mm2 (AWG 14 … AWG 8) conductors. Maximum motor cable length: 25 m shielded or 100 m unshielded.
The integrated filter is Class A. Degree of protection: IP20 / UL open type.
Frame size: FSC. Dimensions: 334 mm height × 189 mm width × 185 mm depth. Net weight: 7.50 kg. The product is without Control Unit and BOP.
Frequently Asked Questions
What is the exact product type and order number?
It is the Siemens 6SL3225-0BE27-5AA1 SINAMICS G120 Power Module PM 250.
What are the LO and HO power ratings?
The LO rated power is 11.00 kW | 15.00 hp, and the HO rated power is 7.50 kW | 10.00 hp.
What input supply does this Power Module use?
The input is 3 AC, 380 … 480 V ±10 % at 47 … 63 Hz.
What is included in the configuration?
The product is without Control Unit and BOP.
Can this line item be included in a project quotation?
Provide the requested quantity, destination, schedule context and any additional BOM lines for quotation review.