Product Overview
Applications
The digital outputs can control a digital input.
Two outputs can be switched in parallel for redundant control of a load.
Technical Summary
| Digital outputs | 64 |
|---|---|
| Rated load voltage | 24 V DC |
| Permissible load voltage range | 20.4 V to 28.8 V DC |
| Rated output current | 0.3 A for signal "1" |
| Output current permissible range | 2.4 mA to 0.36 A for signal "1" |
| Output isolation | In groups of 16; optocoupler isolation to the backplane bus |
| Short-circuit protection | Yes; electronic |
| Output switching frequency | 100 Hz with resistive load; 0.5 Hz with inductive load; 10 Hz on lamp load |
| Required connection | Cable 6ES7392-4Bxx0-0AA0; terminal blocks 6ES7392-1xN00-0AA0 |
| Lifecycle | Product cancellation |
Key Features
64 digital outputs with a 0.3 A rated output current for signal "1".
Digital outputs are isolated in groups of 16; isolation between the channels and backplane bus uses an optocoupler.
Rated load voltage is 24 V DC, with a permissible range from 20.4 V to 28.8 V.
Electronic short-circuit protection is provided, and a green digital output status indicator is available.
Cable 6ES7392-4Bxx0-0AA0 and terminal blocks 6ES7392-1xN00-0AA0 are required.
Product cancellation.
Frequently Asked Questions
What is the exact product model?
It is Siemens 6ES7322-1BP50-0AA0, a SIMATIC S7-300 digital output SM 322.
How many digital outputs does it have?
It has 64 digital outputs, isolated in groups of 16.
What supply voltage and output current apply?
The rated load voltage is 24 V DC, and the rated output current is 0.3 A for signal "1".
Which connection items are required?
Cable 6ES7392-4Bxx0-0AA0 and terminal blocks 6ES7392-1xN00-0AA0 are required.
What should be included with a quotation request?
Include the requested quantity, destination, schedule, and any additional BOM lines.