Product Overview
Technical Summary
| Rated input | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
|---|---|
| Rated power (LO) | 11.00 kW | 15.00 hp |
| Rated power (HO) | 7.50 kW | 10.00 hp |
| Communication | USS/MODBUS RTU |
| I/O interface | 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential input, 1 non-isolated analog output |
| Control techniques | V/f linear / square-law / parameterizable; V/f with flux current control (FCC); V/f ECO linear / square-law; sensorless vector control |
| Safety | Integrated Safe Torque Off |
| Connections | Plug-in screw terminals |
| Protection | IP20 / UL open type |
| Frame size | FSC |
Key Features
3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz.
Low overload: 11.00 kW at 150% 3s, 110% 57s, 100% 240s; high overload: 7.50 kW at 200% 3s, 150% 57s, 100% 240s.
6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential input and 1 non-isolated analog output.
USS/MODBUS RTU fieldbus and integrated Safe Torque Off.
Plug-in screw terminals; IP20 / UL open type protection.
Frame size FSC; 140 mm width, 203 mm depth and 4.40 kg net weight.
Frequently Asked Questions
What is the exact Siemens line item?
The exact product is 6SL3210-1KE22-6UB1, a SINAMICS G120C converter.
What are the low-overload and high-overload ratings?
Low overload is 11.00 kW at 150% 3s, 110% 57s, 100% 240s. High overload is 7.50 kW at 200% 3s, 150% 57s, 100% 240s.
Which communication and I/O interfaces are supplied?
The fieldbus is USS/MODBUS RTU. The interface has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential input and 1 non-isolated analog output.
Which connections and protection are specified?
Connections use plug-in screw terminals. Protection is IP20 / UL open type.
What quantity, destination, schedule and additional BOM lines should be included?
Include the requested quantity, destination, schedule context and any additional BOM lines when submitting the project quotation request.