Product Overview
Applications
Measures voltage signals using the supported voltage input ranges.
Measures current signals from 2-wire transducers using the supported current input ranges.
Provides supply-voltage, wire-break, short-circuit, group-error, and overflow/underflow diagnostics.
Technical Summary
| Product type | AI 4x U/I 2-wire |
|---|---|
| Analog inputs | 4; Differential inputs |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Maximum resolution | 16 bit |
| Voltage input ranges | 0 to +10 V; 1 V to 5 V; -10 V to +10 V; -5 V to +5 V |
| Current input ranges | 0 to 20 mA; 4 mA to 20 mA |
| Conversion time per channel | 180 / 60 / 50 ms |
| BaseUnit compatibility | BU type A0, A1 |
| Module color code | CC03 |
Key Features
4 differential analog inputs support voltage ranges from 0 to +10 V, 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V, plus current ranges of 0 to 20 mA and 4 mA to 20 mA.
Maximum resolution with overrange is 16 bit. Conversion time per channel is 180 / 60 / 50 ms.
Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC. Encoder supply is 24 V with short-circuit protection and maximum output current of 20 mA; maximum 50 mA per channel for a duration < 10 s.
Supports voltage measurement and current measurement as a 2-wire transducer. The maximum burden of a 2-wire transmitter is 650 Ω; 4-wire current measurement is not supported.
Module diagnostics, diagnostic alarm, supply-voltage monitoring, wire-break detection at 4 to 20 mA, short-circuit detection, group error, and overflow/underflow detection are supported.
Fits BU type A0, A1 and uses mechanical coding element Type A. Module-specific color code is CC03.
Frequently Asked Questions
What is the exact input configuration of Siemens 6ES7134-6HD01-0BA1?
It has 4 differential analog inputs for voltage and current signals, with AI 4x U/I 2-wire configuration.
Which signal ranges does this analog input module support?
Voltage ranges are 0 to +10 V, 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V. Current ranges are 0 to 20 mA and 4 mA to 20 mA.
Which BaseUnits and supply voltage are supported?
It supports BU type A0, A1 and a rated supply of 24 V DC within 19.2 V to 28.8 V DC.
Does the configuration support 4-wire current measurement or limit value alarms?
It is without 4-wire current measurement and without limit value alarms. For a quotation, provide the requested quantity, destination, schedule, and any additional BOM lines.