Product Overview
Technical Summary
| Input | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
|---|---|
| Rated power (LO) | 0.75 kW | 1.00 hp |
| Rated power (HO) | 0.55 kW | 0.75 hp |
| Max. output current | 3.40 A |
| Output frequency for vector control | 0 … 240 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| Control techniques | V/f linear / square-law / parameterizable; V/f with flux current control (FCC); V/f ECO linear / square-law; sensorless vector control |
| I/O | 6 standard digital inputs; 1 fail-safe digital input; 1 relay changeover contact; 1 transistor output; 1 differential analog input; 1 non-isolated analog output |
| Communication | PROFINET, EtherNet/IP |
| Protection | IP20 / UL open type |
Key Features
0.75 kW | 1.00 hp at 150% for 3s, 110% for 57s, and 100% for 240s.
0.55 kW | 0.75 hp at 200% for 3s, 150% for 57s, and 100% for 240s.
Supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law, and sensorless vector control. Vector control with sensor and encoderless torque control are not supported.
Includes 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, 1 non-isolated analog output, PROFINET, and EtherNet/IP.
Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Integrated filter: Class A. Degree of protection: IP20 / UL open type.
Frame size FSAA; dimensions: 73 mm width and 160 mm depth; net weight: 1.40 kg (3.09 lb).
Frequently Asked Questions
What are the rated input and output values for 6SL3210-1KE12-3AF2?
Input is 3 AC, 380 … 480 V +10 % -20 % at 47 … 63 Hz. Rated output power is 0.75 kW | 1.00 hp at low overload and 0.55 kW | 0.75 hp at high overload.
Which feedback and control methods does this converter support?
It supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law, and sensorless vector control. Vector control with sensor and encoderless torque control are not supported.
Which communication and I/O interfaces are included?
Communication is PROFINET and EtherNet/IP. The I/O includes 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, and 1 non-isolated analog output.