| Product type | DQ 8x24VDC/0.5A ST |
|---|---|
| Digital outputs | 8 |
| Output type | Source output (PNP, current-sourcing) |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Rated output current | 0.5 A for signal "1" |
| Maximum current per module | 4 A |
| BaseUnit | BU type A0 |
| Short-circuit protection | Yes; Electronic |
| Diagnostics | Wire break; short-circuit to ground and L+; supply voltage; group error |
| Firmware version | V0.0 |
| Product lifecycle | Active Product |
Key Features
8 digital source outputs (PNP, current-sourcing), with parameterizable outputs and 0.5 A rated output current for signal "1".
Rated supply voltage: 24 V DC; permissible supply range: 19.2 V to 28.8 V DC. Rated output voltage: 24 V DC.
Electronic short-circuit protection, open-circuit detection, supply-voltage monitoring, wire-break detection, and diagnostics for short-circuit to ground and L+.
BU type A0 for 1-wire and 2-wire connections; BU type A0 with AUX terminals or a potential distributor module for 3-wire connections; BU type A0 plus a potential distributor module for 4-wire connections.
Maximum current: 0.5 A per channel and 4 A per module. Horizontal installation supports 4 A up to 60 °C; vertical installation supports 4 A up to 50 °C.
Firmware version: V0.0; firmware update: No. STEP 7 TIA V14 with HSP0222 / integrated as of TIA V15; PROFINET GSDML: V2.3.
Frequently Asked Questions
What is the exact Siemens line item and output configuration?
It is Siemens 6ES7132-6BF01-0BA0, a SIMATIC ET 200SP digital output module with 8 source outputs, 24 V DC rated output voltage, and 0.5 A rated output current.
Which BaseUnit connections are supported?
BU type A0 supports 1-wire and 2-wire connections. For 3-wire connections, use BU type A0 with AUX terminals or a potential distributor module; for 4-wire connections, use BU type A0 plus a potential distributor module.
What supply voltage range does the module support?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
What diagnostics are available?
Diagnostics include supply-voltage monitoring, wire-break detection, short-circuit detection to ground and L+, group error indication, and electronic short-circuit protection.