Product Overview
Technical Summary
| Product type | AQ 2xI ST |
|---|---|
| Analog outputs | 2 |
| Output ranges | 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution | Up to 16 bit with overrange, including sign |
| Rated supply voltage | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V DC |
| Cycle time | 1 ms minimum, all channels |
| Maximum load impedance | 500 Ω with current outputs |
| Interfaces and engineering | PROFIBUS GSD Revision 5; PROFINET GSDML V2.3; STEP 7 TIA Portal V13 SP1 / – |
| Firmware version | V1.0.2 |
Key Features
2 analog outputs with 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA ranges.
Up to 16 bit resolution with overrange, including sign.
24 V rated DC supply; permissible range 19.2 V to 28.8 V with reverse polarity protection.
Two-wire actuator connection for current output; maximum load impedance 500 Ω and maximum inductive load 1 mH.
Diagnostics include supply voltage monitoring, wire break, group error, diagnostic alarm, and module-wise overflow/underflow.
Suitable BaseUnits: BU type A0, A1. Color code CC00 and mechanical coding element Type A.
Frequently Asked Questions
What output ranges does 6ES7135-6GB00-0BA1 support?
It supports 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
What supply voltage does this module require?
The rated DC supply is 24 V, with a permissible range of 19.2 V to 28.8 V.
Which BaseUnits are suitable for this configuration?
Suitable BaseUnits are BU type A0 and BU type A1.
What diagnostics are available?
The module provides supply voltage monitoring, wire-break detection, group error, diagnostic alarm, and module-wise overflow/underflow diagnostics.