Product Overview
Applications
The manufacturer declaration states approval for use in hazardous locations.
The manufacturer declaration identifies a maritime application under FM CCC-Ex.
Technical Summary
| Product type | BU type C1 |
|---|---|
| Functional status | FS10 and higher |
| Terminals | Push-in terminal; system-integrated shield connection: Yes; Optional |
| AUX terminals | 2; bridged to the left |
| P1 and P2 bus supply | 24 V |
| AUX bus supply | 24 V; Equal potential group to P1/P2 bus or PE |
| Current carrying capacity | Up to 10 A at up to 60 °C; process terminals: 5 A, or 10 A for process terminals 5 and 6 |
| Process terminals | 16; Pro slot |
| Installation temperature | Horizontal: -30 °C to 60 °C; vertical: -30 °C to 50 °C |
Key Features
Product type designation: BU type C1; HW functional status: FS10 and higher.
The unit has Push-in terminals with 2 AUX terminals bridged to the left.
Supply voltage for the P1 and P2 bus is 24 V; supply voltage for the AUX bus is 24 V with an equal potential group to the P1/P2 bus or PE.
Current carrying capacity is up to 10 A at up to 60 °C; process terminals support up to 5 A, or 10 A for process terminals 5 and 6.
Width: 20 mm; height: 117 mm; depth: 35 mm.
Potential separation exists between the backplane bus and supply voltage and between process terminals and supply voltage; none exists between the power bus and supply voltage.
Frequently Asked Questions
What exact configuration does 6ES7193-6BP20-0BC1 identify?
It identifies a SIMATIC ET 200SP BaseUnit Type C1, BU type C1, with Push-in terminals and 2 AUX terminals bridged to the left.
What bus supply voltage is specified?
The P1 and P2 bus and AUX bus supply voltage is 24 V. The AUX bus is in an equal potential group to the P1/P2 bus or PE.
How many process terminals are provided?
There are 16 process terminals to the I/O module, identified as Pro slot.
What installation temperature range is supported?
For horizontal installation, the ambient temperature during operation is -30 °C to 60 °C. For vertical installation, it is -30 °C to 50 °C.
What should be included in a quotation request for this line item?
Include the requested quantity, destination, schedule context, and any additional BOM lines.