Product Overview
Technical Summary
| Order number | 6SL3210-1KE18-8AF1 |
|---|---|
| Low-overload rated power | 4.00 kW | 5.00 hp |
| High-overload rated power | 3.00 kW | 4.00 hp |
| Input supply | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Communication | PROFINET, EtherNet/IP |
| I/O configuration | 6 digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, 1 non-isolated analog output |
| Control techniques | V/f linear / square-law / parameterizable; V/f with flux current control (FCC); V/f ECO linear / square-law; sensorless vector control |
| Protection | IP20 / UL open type |
Key Features
4.00 kW | 5.00 hp at low overload and 3.00 kW | 4.00 hp at high overload.
Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Output: 3 AC, rated voltage 400V IEC | 480V NEC.
Has V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law, and sensorless vector control.
Has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, 1 non-isolated analog output, PROFINET, and EtherNet/IP.
Has plug-in screw terminals for the line side, motor end, and DC link. Protection: IP20 / UL open type.
Frame size: FSA. Dimensions: 73 mm width x 200 mm depth. Net weight: 1.70 kg (3.75 lb).
Frequently Asked Questions
What is the low-overload rated power of 6SL3210-1KE18-8AF1?
The low-overload rated power is 4.00 kW | 5.00 hp.
Which communication interfaces does this converter have?
It has PROFINET and EtherNet/IP communication.
What I/O configuration does this line item have?
It has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, and 1 non-isolated analog output.
What are the mechanical configuration and protection details?
The frame size is FSA, the dimensions are 73 mm width x 200 mm depth, and protection is IP20 / UL open type.