Product Overview
Technical Summary
| Order number | 6SL3210-1KE15-8AP2 |
|---|---|
| Product family | SINAMICS G120C |
| Input supply | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Rated output power, low overload | 2.20 kW | 3.00 hp |
| Rated output power, high overload | 1.50 kW | 2.00 hp |
| Communication | PROFIBUS DP |
| Digital inputs | 6 standard digital inputs and 1 fail-safe digital input |
| Analog I/O | 1 differential analog/digital input, 10 bit; 1 non-isolated analog output |
| Protection | IP20 / UL open type |
| Frame size | FSAA |
Key Features
2.20 kW | 3.00 hp at low overload; 1.50 kW | 2.00 hp at high overload.
3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz.
Low overload: 150% for 3s, 110% for 57s, 100% for 240s. High overload: 200% for 3s, 150% for 57s, 100% for 240s.
6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog/digital input and 1 non-isolated analog output.
PROFIBUS DP communication; IP20 / UL open type.
Frame size FSAA; width 73 mm, depth 155 mm; plug-in screw terminals for line-side, motor-end and DC link connections.
Frequently Asked Questions
What is the exact product identified by this line item?
It is Siemens SINAMICS G120C, order number 6SL3210-1KE15-8AP2.
What are the low-overload and high-overload output ratings?
Low overload is 2.20 kW | 3.00 hp; high overload is 1.50 kW | 2.00 hp. The overload profiles are 150% for 3s, 110% for 57s, 100% for 240s at low overload, and 200% for 3s, 150% for 57s, 100% for 240s at high overload.
Which communication and I/O interfaces are provided?
Communication is PROFIBUS DP. The I/O includes 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog/digital input and 1 non-isolated analog output.
What are the mounting dimensions and protection designation?
The frame size is FSAA, with 73 mm width and 155 mm depth. Protection is IP20 / UL open type.
What project details should accompany a quotation request?
Provide the requested quantity, destination, schedule context and any additional BOM line items.