Product Overview
Applications
Supports counting with 1 counter input and 32-bit counter data.
Supports frequency measurement up to 100 kHz and speed measurement up to 25 000 1/min.
Supports cycle duration measurement from 10 μs to 120 s.
Technical Summary
| Product type | SIMATIC DP electronics module for ET 200S |
|---|---|
| Supply voltage | 24 V DC rated; permissible range 20.4 V to 28.8 V |
| Digital inputs | 1; gate control, synchronization and latch function |
| Digital outputs | 1; controls a digital input |
| Measurement range | Frequency: 0.1 Hz to 100 kHz; cycle duration: 10 μs to 120 s; speed: 1 1/min to 25 000 1/min |
| Encoder connection | Up to 1; incremental encoder (asymmetrical), 24 V initiator or 2-wire sensor |
| Counter input | 1; 32 bit |
| Output current | 5 mA to 2 000 mA at 0 to 40 °C; 5 mA to 500 mA at 0 to 60 °C; 1 000 mA at 50 °C |
| Diagnostics | Diagnostics function and group error SF, digital input, digital output, forward counting and backward counting LEDs |
| Lifecycle | Product cancellation |
Key Features
Supports counting, frequency measurement from 0.1 Hz to 100 kHz, cycle duration measurement from 10 μs to 120 s, and speed measurement from 1 1/min to 25 000 1/min.
Has 1 digital input and 1 digital output. The digital input supports gate control, synchronization and latch function.
Connects up to 1 encoder, including an incremental encoder (asymmetrical), 24 V initiator or 2-wire sensor.
Rated load voltage is 24 V DC, with a permissible range from 20.4 V to 28.8 V, reverse polarity protection and encoder supply short-circuit protection.
The output current for signal "1" is 5 mA to 2 000 mA for 0 to 40 °C, and 5 mA to 500 mA for 0 to 60 °C; 1 000 mA is available at 50 °C.
Has a 15 mm installation width, dimensions of 15 mm × 81 mm × 52 mm, and diagnostics with group error SF and digital input, digital output, forward counting and backward counting status LEDs.
Frequently Asked Questions
What is the exact product represented by 6ES7138-4DA04-0AB0?
It is a SIMATIC DP electronics module for ET 200S with 1 digital input, 1 digital output, counting and measurement functions.
What supply voltage does this module use?
The rated load voltage is 24 V DC, with a permissible range from 20.4 V to 28.8 V.
How many encoders can be connected?
Up to 1 encoder can be connected, including an incremental encoder (asymmetrical), 24 V initiator or 2-wire sensor.
What are the module dimensions and installation width?
The installation width is 15 mm. The dimensions are 15 mm × 81 mm × 52 mm.
Can you include this line item in a project quotation request?
Yes. Submit the requested quantity, destination, schedule context and any additional BOM lines for quotation handling.