Product Overview
Technical Summary
| Product lifecycle | Active Product |
|---|---|
| Input supply | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Rated power (LO) | 1.10 kW | 1.50 hp |
| Rated power (HO) | 0.75 kW | 1.00 hp |
| Communication | PROFIBUS DP |
| Digital inputs | 6 standard digital inputs; 1 fail-safe digital input |
| Analog I/O | 1 differential analog input, 10 bit; 1 non-isolated analog output |
| Control methods | V/f linear / square-law / parameterizable; V/f with flux current control (FCC); V/f ECO linear / square-law; sensorless vector control |
| Connections | Plug-in screw terminals for line side, motor end, and DC link |
| Protection | IP20 / UL open type |
Key Features
3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz; rated input current is 4.10 A for low overload and 3.20 A for high overload.
Low overload: 1.10 kW | 1.50 hp at 3.10 A. High overload: 0.75 kW | 1.00 hp at 2.20 A.
Supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law, and sensorless vector control. Vector control with sensor and encoderless torque control are not supported.
6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, 1 non-isolated analog output, and PROFIBUS DP.
Plug-in screw terminals are provided for the line side, motor end, and DC link. Protection: IP20 / UL open type; integrated Class A filter.
Frame size FSAA; dimensions are 73 mm width and 155 mm depth; net weight is 1.40 kg.
Frequently Asked Questions
What is the exact Siemens line item?
The exact line item is 6SL3210-1KE13-2AP2, a SINAMICS G120C compact converter.
What are the low-overload and high-overload power ratings?
Low overload is 1.10 kW | 1.50 hp at 3.10 A. High overload is 0.75 kW | 1.00 hp at 2.20 A.
Which control and feedback functions are supported?
It supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law, and sensorless vector control. Vector control with sensor and encoderless torque control are not supported.
Which communication and I/O interfaces are included?
The unit has PROFIBUS DP, 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, and 1 non-isolated analog output.
What project details should accompany a quotation request?
Provide the requested quantity, destination, schedule context, and any additional BOM line items.