Product Overview
Technical Summary
| Product lifecycle | Active Product |
|---|---|
| Input supply | 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz |
| Rated power, HO | 37.00 kW | 50.00 hp |
| Rated power, LO | 45.00 kW | 60.00 hp |
| Rated current, HO | 75.00 A |
| Rated current, LO | 90.00 A |
| Output frequency, vector control | 0 … 200 Hz |
| Output frequency, V/f control | 0 … 550 Hz |
| Integrated filter | Class A |
| Protection | IP20 / UL open type |
| Frame size | FSE |
| Configuration exclusion | Without control unit and BOP |
Key Features
Rated power: 37.00 kW | 50.00 hp HO; rated current: 75.00 A HO.
Rated power: 45.00 kW | 60.00 hp LO; rated current: 90.00 A LO.
Input: 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz.
Output frequency: 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control.
Line-side and motor-end connections use M6 bolts with 10.00 … 50.00 mm2 (AWG 8 … AWG 1) conductors. Maximum motor cable length is 50 m (164.04 ft) shielded or 100 m (328.08 ft) unshielded.
Frame size: FSE; dimensions: 275 mm (10.83 in) W × 635 mm (25.00 in) H × 204 mm (8.03 in) D; protection: IP20 / UL open type. Without control unit and BOP.
Frequently Asked Questions
What are the HO and LO output ratings for 6SL3225-0BE33-7AA0?
HO output is 37.00 kW | 50.00 hp at 75.00 A. LO output is 45.00 kW | 60.00 hp at 90.00 A.
What input supply does this power module use?
The input is 3 AC, 380 … 480 V ±10 % at 47 … 63 Hz.
What connection and motor-cable details should be retained in the BOM?
Line-side and motor-end connections use M6 bolts and 10.00 … 50.00 mm2 (AWG 8 … AWG 1) conductors. Maximum motor cable length is 50 m (164.04 ft) shielded or 100 m (328.08 ft) unshielded.
What is included in this configuration?
It is without a control unit and BOP.
What quantity, destination, schedule, and additional BOM lines should be included in a quotation request?
Include the requested quantity, destination, schedule context, and any additional BOM line items with this exact product number.