Product Overview
Technical Summary
| Rated power (LO) | 3.00 kW | 4.00 hp |
|---|---|
| Rated power (HO) | 2.20 kW | 3.00 hp |
| Input | 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz |
| Output frequency for vector control | 0 … 200 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| Overload ratings | LO: 150% 3s, 110% 57s, 100% 240 s at -10 … 40 °C; HO: 200% 3s, 150% 57s, 100% 240 s at -10 … 50 °C |
| Connections | Plug-in screw terminals; 1.50 … 2.50 mm2 (AWG 16 … AWG 14) |
| Integrated functions | Class A filter and braking chopper |
| Protection | IP20 / UL open type |
| Exclusions | Without Control Unit and operating unit |
Key Features
Rated power is 3.00 kW | 4.00 hp for low overload and 2.20 kW | 3.00 hp for high overload. Low overload is 150% for 3s, 110% for 57s and 100% for 240 s at -10 … 40 °C; high overload is 200% for 3s, 150% for 57s and 100% for 240 s at -10 … 50 °C.
Input: 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz.
The module has an integrated Class A filter and braking chopper.
Output frequency is 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control.
Line-side and motor-end connections use plug-in screw terminals for 1.50 … 2.50 mm2 (AWG 16 … AWG 14) conductors. Maximum motor cable length is 50 m (164.04 ft) shielded or 100 m (328.08 ft) unshielded.
Frame size FSA, IP20 / UL open type, dimensions 73 mm (2.87 in) wide × 196 mm (7.72 in) high × 165 mm (6.50 in) deep. It is without a Control Unit and operating unit.
Frequently Asked Questions
What is the exact product and supplied configuration?
It is the Siemens 6SL3210-1PE18-0AL1 SINAMICS Power Module PM240-2 with an integrated Class A filter and braking chopper. It is without a Control Unit and operating unit.
What input supply does this Power Module use?
Input is 3 AC, 380 … 480 V ±10 % at 47 … 63 Hz.
What are the low-overload and high-overload ratings?
Low overload: 3.00 kW | 4.00 hp, with 150% for 3s, 110% for 57s and 100% for 240 s at -10 … 40 °C. High overload: 2.20 kW | 3.00 hp, with 200% for 3s, 150% for 57s and 100% for 240 s at -10 … 50 °C.
What connections and motor cable lengths are supported?
Line-side and motor-end connections use plug-in screw terminals with 1.50 … 2.50 mm2 (AWG 16 … AWG 14) conductors. Maximum motor cable length is 50 m (164.04 ft) shielded or 100 m (328.08 ft) unshielded.