Technical Summary
| Product lifecycle | Product cancellation |
|---|---|
| Digital outputs | 8 |
| Rated load voltage | 24 V |
| Permissible load-voltage range | 20.4 V to 28.8 V |
| Rated output current for signal "1" | 0.5 A |
| Output current range for 0 to 40 °C | 10 mA to 0.6 A |
| Output current range for 40 to 60 °C | 10 mA to 0.6 A |
| Short-circuit protection | Yes; Electronic |
| Required front connector | 20-pin |
| Total output current per group, horizontal installation | 4 A up to 40 °C; 3 A up to 60 °C |
Key Features
SM 322 provides 8 digital outputs with potential separation between channels in groups of 8 and optocoupler separation from the backplane bus.
Rated load voltage is 24 V, with a permissible range from 20.4 V to 28.8 V.
Output current for signal "1" has a rated value of 0.5 A; the permissible range is 10 mA to 0.6 A for 0 to 40 °C and 40 to 60 °C.
The outputs have electronic short-circuit protection, parameterizable diagnostics and diagnostic alarms, plus wire-break, short-circuit, and missing-load-voltage diagnosis.
A 20-pin front connector is required for connection.
The module measures 40 mm wide, 125 mm high, and 120 mm deep; weight is approximately 210 g.
Frequently Asked Questions
What is the exact Siemens line item and output configuration?
It is Siemens SIMATIC 6ES7322-8BF00-0AB0, an SM 322 isolated digital output module with 8 digital outputs.
What supply voltage and output current does this module support?
The rated load voltage is 24 V, with a permissible range from 20.4 V to 28.8 V. The rated output current for signal "1" is 0.5 A.
Which connector is required for installation?
A 20-pin front connector is required.
Does the module include fuse-blown diagnosis?
No. Fuse-blown diagnosis is not available; wire-break, short-circuit, and missing-load-voltage diagnosis are available.