Product Overview
Applications
Measures voltage, current, energy, frequency, active power and reactive power.
Technical Summary
| Product type | AI energy meter 400VAC ST |
|---|---|
| Firmware version | V3.0 |
| Usable BaseUnit | BU type D0 |
| Supply voltage | 100 – 240 V AC; permissible range 90 V to 264 V |
| Voltage measurement | 230 V phase-to-neutral; 400 V between line conductors |
| Current measurement | 5 % to 100 % of secondary rated current; 1 A, 5 A |
| Measurement bandwidth | 2 kHz |
| Cycle time | 50 ms, all channels |
| Measurement category | CAT II; CAT III with guaranteed protection level of 1.5 kV |
| Installation | Any mounting position |
| Product lifecycle | Product cancellation |
Key Features
Measures voltage, current, energy, frequency, active power and reactive power.
Measures 230 V between phase and neutral conductor and 400 V between line conductors; measurable ranges are 90 V to 264 V and 155 V to 460 V respectively.
Measures 5 % to 100 % of the secondary rated current for 1 A or 5 A; current measurement with a current transformer is supported.
TRMS measurement with a 2 kHz bandwidth and a typical 50 ms cycle time for consistent updating of all measured and calculated values.
Provides channel diagnostics, diagnostic alarms, green channel-status LED, red Fn LED and green/red DIAG LED. PROFIBUS uses GSD Revision 5 and PROFINET uses V2.3.
Suitable for BU type D0, with any mounting position; dimensions are 20 mm wide, 73 mm high and 58 mm deep.
Frequently Asked Questions
What is the exact product type of 6ES7134-6PA01-0BD0?
It is an AI energy meter 400VAC ST analog input module for SIMATIC ET 200SP, suitable for BU type D0.
Which voltage ranges does this module measure?
It measures 230 V between phase and neutral conductor and 400 V between line conductors; the permissible ranges are 90 V to 264 V and 155 V to 460 V respectively.
What is included in the current-measurement configuration?
Current measurement is supported with a current transformer. The configuration is without a voltage transformer.
How should this line item be quoted for a project?
Provide the requested quantity, destination, schedule context and any additional BOM lines for the quotation request.