Product Overview
Technical Summary
| Product lifecycle | Active Product |
|---|---|
| Input | 3 AC; 380 … 480 V +10 % -20 %; 47 … 63 Hz |
| Rated power, low overload | 15.00 kW | 20.00 hp |
| Rated power, high overload | 11.00 kW | 15.00 hp |
| Communication | PROFIBUS DP |
| Digital inputs | 6 standard; 1 fail-safe |
| Analog I/O | 1 differential analog input, 10 bit; 1 non-isolated analog output |
| Control techniques | V/f linear / square-law / parameterizable; V/f with flux current control (FCC); V/f ECO linear / square-law; sensorless vector control |
| Safety | Integrated Safe Torque Off |
| Connections | Plug-in screw terminals; line side and DC link conductor cross-section 6.00 … 16.00 mm2 (AWG 10 … AWG 6) |
| Mechanical and protection | FSC; 140 mm width; 203 mm depth; IP20 / UL open type |
Key Features
15.00 kW | 20.00 hp at low overload and 11.00 kW | 15.00 hp at high overload.
3 AC input, line voltage 380 … 480 V +10 % -20 %, and line frequency 47 … 63 Hz.
PROFIBUS DP communication; V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law, and sensorless vector control are supported.
6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, 1 non-isolated analog output, and integrated Safe Torque Off.
Plug-in screw terminals are provided on the line side, motor end and DC link for a braking resistor. Protection is IP20 / UL open type.
FSC frame size, 140 mm width, 203 mm depth, and 4.40 kg net weight.
Frequently Asked Questions
What is the exact Siemens line item?
It is Siemens 6SL3210-1KE23-2UP1, a SINAMICS G120C compact converter with PROFIBUS DP and integrated Safe Torque Off.
What input ratings should be retained for quotation verification?
The input is 3 AC, 380 … 480 V +10 % -20 %, at 47 … 63 Hz.
Which control and feedback functions are supported?
It supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law, and sensorless vector control. Vector control with sensor and encoderless torque control are not supported.
Which connections and protection details apply?
It has plug-in screw terminals on the line side, motor end and DC link for a braking resistor. Protection is IP20 / UL open type.
How should this item be included in a project request?
Submit the requested quantity, destination, schedule context and any additional BOM line items with the exact order number.