Product Overview
Applications
Used for deterministic data exchange between PN Controllers and between PROFINET subnets.
Used for PROFIsafe data exchange between connected PROFINET subnet segments.
Technical Summary
| Product type | PN/PN coupler |
|---|---|
| Firmware version | V6.0 |
| Supply voltage | 24 V DC; permissible range 19.2 V to 28.8 V DC |
| PROFINET interfaces | 2; via BusAdapter |
| Transmission rate | 100 Mbit/s |
| Address space per station, max. | 1 440 byte; per input / output |
| Number of submodules per station, max. | 116 |
| Mounting | Mounting rail 7.5 mm and 15 mm |
| BusAdapter | SIMATIC BusAdapter; delivery without BusAdapter |
| STEP 7 TIA Portal | Configurable/integrated from version V20 or higher |
| Product lifecycle | Active Product |
Key Features
Supports data exchange between max. 4 PN Controllers per subnet and from subnet to subnet, including PROFIsafe data exchange.
Supports I/O, MSI, MSO, and data record communication, with PROFINET IO Device, Open IE communication, IRT, and Dynamic Frame Packing.
Provides 2 PROFINET interfaces and 2 ports via SIMATIC BusAdapter, with transmission up to 100 Mbit/s.
Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC; redundant power supply and reverse polarity protection.
Mounting: mounting rail 7.5 mm and 15 mm. Delivery is without BusAdapter.
Frequently Asked Questions
What is Siemens 6ES7158-3AD10-0XA0?
It is a SIMATIC PN/PN Coupler with product type designation PN/PN coupler.
What supply voltage does the PN/PN Coupler use?
Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
How is the PROFINET connection provided?
The PROFINET connection is provided via SIMATIC BusAdapter, with 2 interfaces and 2 ports.
Is the BusAdapter included in this configuration?
It is without BusAdapter.
What should be included in a quotation request for this line item?
Include the requested quantity, destination, schedule context, and any additional BOM lines.