Product Overview
Applications
Monitors the STOP button, emergency stop button and acknowledgement button through direct wiring or PROFIsafe.
Connects Mobile Panels using PROFINET and supports safety relay connection and terminal detection.
Technical Summary
| Product type | Connection box |
|---|---|
| Mounting | Wall mounting/direct mounting |
| Supply voltage | 24 V DC; permissible range 19.2 V DC to 28.8 V DC |
| Current consumption | 96 mA rated value |
| Active power input | 2.3 W, typ. |
| Industrial Ethernet interfaces | 3 |
| PROFINET interfaces | 3 |
| Protocols | PROFINET, PROFIsafe, EtherNet/IP, TCP/IP, DHCP, SNMP, DCP, LLDP, MODBUS |
| Protection | IP65 |
Key Features
Connection box Standard for Mobile Panels.
Supports safety evaluation through direct wiring and PROFIsafe, including monitoring of the STOP button, emergency stop button and acknowledgement button.
Has 3 industrial Ethernet interfaces and 3 PROFINET interfaces; supports PROFINET, PROFIsafe, EtherNet/IP, TCP/IP, DHCP, SNMP, DCP, LLDP and MODBUS.
24 V DC rated supply, with a permissible range from 19.2 V DC to 28.8 V DC.
Supports wall mounting/direct mounting and has IP65 protection.
It does not support control cabinet installation, IRT, MRP, AS-Interface or EIB/KNX.
Frequently Asked Questions
What is the exact product type of 6AV2125-2AE13-0AX0?
It is a Siemens SIMATIC HMI connection box Standard for Mobile Panels.
What supply voltage does the connection box use?
It has a 24 V DC rated supply and a permissible range from 19.2 V DC to 28.8 V DC.
Which interfaces and protocols are supported?
It has 3 industrial Ethernet interfaces and 3 PROFINET interfaces. Supported protocols include PROFINET, PROFIsafe, EtherNet/IP, TCP/IP, DHCP, SNMP, DCP, LLDP and MODBUS.
How is the connection box mounted and protected?
It supports wall mounting/direct mounting and has IP65 protection.
What configuration exclusions should be retained in a quotation request?
It is without control cabinet installation, IRT, MRP, AS-Interface and EIB/KNX support.