Product Overview
Technical Summary
| Digital inputs | 8; parameterizable |
|---|---|
| Rated input voltage | 24 V DC |
| Signal "0" input voltage | -30 to +5 V |
| Signal "1" input voltage | +11 to +30 V |
| PROFINET interfaces | 1; 100 Mbit/s full duplex |
| M12 ports | 2; 4-pin, D-coded |
| Supported protocols | PROFINET IO, EtherNet/IP, Modbus TCP |
| Encoder supply outputs | 8; 100 mA max. per output |
| Input delay | 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms |
| Firmware version | V5.1.x |
| Protection degree | IP65/67/69K |
| Product lifecycle | Active Product |
Key Features
The device has 8 parameterizable digital inputs with a type 3 input characteristic according to IEC 61131.
Rated input voltage is 24 V DC, with a permissible range from -30 to +5 V for signal "0" and +11 to +30 V for signal "1".
It has 1 PROFINET interface with 100 Mbit/s full duplex, an integrated switch, and 2 M12, 4-pin, D-coded ports.
Supported protocols include PROFINET IO, EtherNet/IP, and Modbus TCP. PROFIsafe is not supported.
Channel diagnostics include wire break and encoder power supply short-circuit detection. Protection is IP65/67/69K.
Frequently Asked Questions
What is the exact configuration of 6ES7141-6BG00-0BB0?
It is a SIMATIC ET 200eco PN device with DI 8x 24 V DC, M12-L, 8x M12, single and double assignment, and input type 3 according to IEC 61131.
Which communication protocols does this device support?
It supports PROFINET IO, EtherNet/IP, and Modbus TCP. PROFIsafe is not supported.
What interfaces and connectors are included in the specification?
The device has 1 PROFINET interface, an integrated switch, and 2 M12, 4-pin, D-coded ports.
What diagnostics are available?
Channel diagnostics support wire break detection at the input and encoder power supply short-circuit detection. Diagnostic, maintenance, and hardware interrupts are parameterizable.